Assemblies
-
Technical committeeTypeAcronymIEC 62271-214CommitteePublished year2019Description
IEC 62271-214:2019 specifies requirements for internal arc classification of metal-enclosed pole-mounted switchgear installations used for alternating current with rated voltages above 1 kV and up to and including 52 kV with service frequencies up to and including 60 Hz. This document is applicable to three-phase, two-phase and single phase equipment. Enclosures may include fixed and removable components and may be filled with fluid (liquid or gas) to provide insulation.
-
Technical committeeTypeAcronymIEC 62271-212CommitteePublished year2016KeywordsDescription
IEC 62271-212:2016 specifies the service conditions, rated characteristics, general structural requirements and test methods of the assemblies of the main electrical functional units of a high-voltage/low-voltage distribution substation, duly interconnected, for alternating current of rated operating voltages above 1 kV and up to and including 52 kV on the high-voltage side, service frequency 50 Hz or 60 Hz. This assembly is to be cable-connected to the network, and intended for installation within an indoor or outdoor closed electrical operating area.
This publication is to be read in conjunction with IEC 62271-1:2007
-
Technical committeeTypeAcronymIEC 62271-211CommitteePublished year2014Description
IEC 62271-211:2014 is applicable to single and three phase direct connections between gas-insulated metal-enclosed switchgear (GIS) for rated voltages above 52 kV and transformer arrangements to establish electrical and mechanical interchange ability and to determine the limits of supply of for the transformer connection. This first edition cancels and replaces the first edition of IEC TR 61639:1996 and constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
a) transfer from technical report to international standard;
b) the minimum voltage rating was changed from 72,5 kV to above 52 kV;
c) update of normative references;
d) definition of insulated junction including limit of supply;
e) definition of dielectric test of gas-insulated metal-enclosed switchgear for transformer connection in a three phase enclosure;
f) addition of interface tolerances at transformer side;
g) addition of transformer tolerances in service;
h) addition of exceptional loads for bushings and flanges;
i) consideration of oil- and gas-insulated transformers;
j) inclusion of three-phase enclosed direct connections. The contents of the corrigendum 1 of August 2015 and corrigendum 2 of August 2017 have been included in this copy. -
Technical committeeTypeAcronymIEC 62271-209CommitteePublished year2019Description
IEC 62271-209:2019 RLV contains both the official IEC International Standard and its Redline version. The Redline version is available in English only and provides you with a quick and easy way to compare all the changes between the official IEC Standard and its previous edition.
IEC 62271-209:2019 covers the connection assembly of fluid-filled and extruded cables to gas-insulated metal enclosed switchgear (GIS), in single- or three-phase arrangements where the cable terminations are fluid-filled or dry-type and there is a separating insulating barrier between the cable insulation and the gas insulation of the switchgear. This second edition cancels and replaces the first edition published in 2007. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
a) New numbering in accordance with ISO/IEC directives, Part 2 (2016) and to IEC 62271‑1:2017;
b) Clause 3: addition of a definition for plug-in cable termination, filling pressure and minimum function pressure for insulation;
c) Clause 7: An additional dielectric type test for plug-in cable termination was added; also a pressure type test as well as a leak rate test on the insulator of a cable termination was implemented;
d) Clause 12: New clause about safety practices;
e) Clause 13: New clause about influence of the product on the environment;
f) New informative Annex A: Mechanical forces applied on the flange of the cable connection enclosure. -
Technical committeeTypeAcronymIEC 62271-207CommitteePublished year2012Description
IEC 62271-207:2012 applies to gas-insulated switchgear assemblies for alternating current of rated voltages above 52 kV for indoor and outdoor installations, including their supporting structure. This second edition of IEC 62271-207 cancels and replaces the first edition published in 2007. It constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
- modification of the minimum voltage rating from 72,5 kV to above 52 kV;
- harmonisation of qualification procedures for GIS with IEEE 693:2005 Annex A and P by modifying the response spectra;
- modification of the test procedures;
- addition of criteria of allowed stresses;
- addition of dynamic analysis CQC. The contents of the corrigendum of January 2013 have been included in this copy. -
Technical committeeTypeAcronymIEC 62271-206CommitteePublished year2011Description
IEC 62271-206:2011 is applicable to voltage presence indicating systems (VPIS) incorporated in a.c. switchgear and controlgear covered by IEC 62271-200 or IEC 62271-201. Voltage presence indicating systems are devices used to provide information to operators about the voltage condition of the main circuit of the switchgear in which they are installed. This first edition of IEC 62271-206 cancels and replaces the first edition of IEC 61958. This edition constitutes a minor revision. The main changes with respect of the first edition of IEC 61958 are an actualization of references and the degree of protection which has been changed from IPXXB to IP2X.
-
Technical committeeTypeAcronymIEC 62271-205CommitteePublished year2008Description
This part of IEC 62271 applies to compact switchgear assemblies consisting of at least one switching device directly connected to, or sharing components with, one or more other devices such that there is an interaction between the functions of the individual devices. Such assemblies are made up of devices defined in 1.101 and are designed, tested and supplied for use as a single unit. The interaction between devices may be due to proximity, sharing of components or a combination of both. The assemblies may contain components of air insulated switchgear (AIS) only or a combination of AIS and gas insulated switchgear (GIS), so called mixed technology switchgear (MTS) and may be delivered entirely prefabricated or partially assembled.
-
Technical committeeTypeAcronymIEC 62271-204CommitteePublished year2011Description
IEC 62271-204:2011 applies to rigid HV gas insulated transmission lines (GIL) in which the insulation is obtained, at least partly, by a non-corrosive insulating gas, other than air at atmospheric pressure, for alternating current of rated voltages above 52 kV, and for service frequencies up to and including 60 Hz. This standard cancels and replaces IEC/TS 61640:1998. It is a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
- update to be in line with IEC 62271-1:2007 and 62271-203 and alignment of the voltage ratings and the test voltages;
- addition of new information for gas tightness and corrosion protection.This publication is to be read in conjunction with IEC 62271-1:2007.
-
Technical committeeTypeAcronymIEC 62271-203CommitteePublished year2011Description
IEC 62271-203:2011 specifies requirements for gas-insulated metal-enclosed switchgear in which the insulation is obtained, at least partly, by an insulating gas other than air at atmospheric pressure, for alternating current of rated voltages above 52 kV, for indoor and outdoor installation, and for service frequencies up to and including 60 Hz. This second edition of IEC 62271-203 cancels and replaces the first edition of IEC 62271-203, published in 2003, and constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
- adopting the structure and the content to IEC 62271-1,
- harmonisation with IEEE C37.122,
- addition of the new Annex F and the new Annex G.This publication is to be read in conjunction with IEC 62271-1:2007. The contents of the corrigendum of July 2013 have been included in this copy.
-
Technical committeeTypeAcronymIEC 62271-202CommitteePublished year2014Description
IEC 62271-202:2014 specifies the service conditions, rated characteristics, general structural requirements and test methods of high voltage/low voltage or low voltage/high voltage prefabricated substations, which are cable-connected, to be operated from inside (walk-in type) or outside (non-walk-in type) for alternating current of rated voltages above 1 kV and up to and including 52 kV on the high voltage side, and for one or more transformers for service frequencies up to and including 60 Hz for outdoor installation at locations with public accessibility and where protection of personnel is provided. This second edition cancels and replaces the first edition published in 2006. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
a) regarding temperature-rise test an alternative method for liquid filled transformers is (re)introduced and the temperature-rise test method for dry-type transformers is specified more precisely;
b) testing procedure for short time and peak withstand current tests are specified more precisely;
c) assessment of electromagnetic fields is considered including a type test (optional) according IEC/TR 62271-208:2009;
d) influence of the product on the environment is considered (Clause 12);
e) internal arc test requirements have been adapted to IEC 62271-200:2011 and requirements for the assessment of pressure relief volumes below the floor / ground has been assigned;
f) the method for defining the load factor in an enclosure for liquid filled transformers is extended with different temperature rises for the transformer outside the enclosure (Annex DD);
g) for the calculation of the load factor of dry-type transformers in an enclosure the insulation systems according to IEC 60076-1:2011, Tables B.1 and B.2 are worked out in detail.This publication is to be read in conjunction with IEC 62271-201:2007. The contents of the corrigendum of April 2015 have been included in this copy.